Congratulations, your trade-in discount has been applied. smb
<%= title %> <% if (!!discountAmount) { %> <%= discountAmount %> <% } %> <% if (!!tradeInAmount && !!additionalDiscount) { %> <%= tradeInAmount %> <%= additionalDiscount %> <% } %>
<%= deviceSummary %>
<% if (quantityChangeable) { %>
Add Samsung Care+ for Business
Learn moreYou love it, we cover it. Protection for your new Galaxy device from the people who know it best
Please select Samsung Care + for Business or "No Coverage"
-
<% options.forEach((option) => { %>
-
<% if(hasChildren) { %>
<% } else { %> <% } %>
<% }) %>
*All prices include insurance premium tax
World Top Energy Efficiency
Samsung DVM S offers higher energy efficiency and easy to install models that keep your business moving forward.
Reduce expenses with installation designed to be easy and flexible
At 22 horsepower (HP), the large-unit capacity of the DVM S facilitates economical installation with a smaller footprint and lighter weight. Non-polar communication between indoor and outdoor units promotes easier wiring work. Non-polar communication is safer because the outdoor unit protects itself if the communication cable is mistakenly connected to a power terminal. The DVM S provides extended piping length of up to 220 m (721.79 ft), with no decrease in performance. With this technology, installation is available for a maximum height of 110 m (360.89 ft), the equivalent of 20 stories. The piping distance is far between outdoor and indoor units, so individual indoor units perform capacity connection control and automatic refrigerant equalization. This process promotes balanced performance between the units.
Achieve high energy efficiency with the DSI system
DSI is a third-generation system that uses a Dual Inverter Compressor. The compressor upgrades refrigerant flow and the motor’s operating performance. With this system, DSI achieves high energy efficiency. The two compressors operate in unison so that overall compressor durability is preserved for a longer time. With compressor speed acceleration and simultaneous starting, DVM S provides rapid cooling and heating performance. In addition, DVM S promotes stable, equal oil balancing without the need for an additional balancing pipe.
Lessen disruptions with 12-hour quiet operation
DVM S outdoor fans include an operation control system that drastically reduces noise levels. Quiet operation continues for 12 hours, so users can take advantage of decreased distractions during the night.
Discover and fix problems readily with Auto Commissioning Management (ACM)
DVM S has a smart management system that facilitates self-diagnosis, auto commissioning, auto management and mobile data transmission. DVM S monitors the operation status and displays an error code in response to signs of abnormal operation, enabling users to readily address the problem. If a malfunction occurs with the DVM S outdoor unit, the last 30 minutes of operating data are stored for automatic backup. Small openings on the front of the outdoor unit promote straightforward unit status checking and option setting. With S-Checker, users can control the system with a smartphone or tablet PC, so management is simplified and convenient. ACM promotes reduced commissioning time for DVM S, at just 50 minutes. Testing results are automatically stored and reported.
Specifications
Specifications Detail
Features
- Type DVM S (HR)
Model Name
- Outdoor Unit AM160FXVAGR/EU
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
- 3,4,380 - 415,50
System
- Mode HEAT RECOVERY
Performance (nominal)
- 16HP
Capacity
- Cooling [kW] 45
- Cooling [Btu/h] 153,500
- Heating [kW] 50
- Heating [Btu/h] 170,600
Power Input (Nominal)
- Cooling 1) 11kW
- Heating 2) 11.5kW
Current Input (Nominal)
- Cooling 1) 17.6A
- Heating 2) 18.4A
Power
- MCA [A] 40 (MCA)
- MFA [A] 40
Energy Efficiency
- EER (Nominal Cooling) 4.09
- COP (Nominal Heating) 4.35
Compressor
- Type SSC Scroll x 2
- Output(kW) (4.96 x 2)
- Model DS-GB052FAVASG x 2
- Oil (Type) PVE
- Oil (Initial Charge) [cc] 4000
Fan
- Type Propeller
- Motor (Output) [W] 620 x 2
- Air Flow Rate (High / Mid / Low) [CMM] 250
- Air Flow Rate(High/Mid/Low)[L/S] 4,333.33
- External Static Pressure (Min / Std / Max) [mmAq] 8
- External Static Pressure (Min / Std / Max) [Pa] 78.45
Piping Connections
- Liquid Pipe (Φ, mm) 12.7
- Gas Pipe (Φ, mm) 28.58
- Discharge Gas Pipe (Φ, mm) 22.22
- Installation Max. Length [m] 200 (220)
- Installation Max. Height [m] 110 (40)
Field Wiring
- Transmission Cable 0.75 ~ 1.5
Refrigerant
- Type R410A
- Factory Charging (kg) 7.4
Sound
- Sound Pressure 63dBA
- Sound Power 83dBA
External Dimension (Outdoor Unit)
- Net Weight 284
- Shipping Weight (kg) 303
- Net Dimensions (WxHxD) (mm) 1,295 x 1,695 x 765
- Shipping Dimensions (WxHxD) (mm) 1,363 x 1,887 x 832
Operating Temp. Range
- Cooling (℃) -15 ~ 48
- Heating (℃) -20 ~ 24